ErP Directive
The ErP Directive 2009/125/EC sets forth minimum requirements for energy-relevant products in order to adhere to the EU's predefined climate goals. The implementation of these requirements takes place for motors according to regulation (EU) No. 640/2009, and for fans according to (EU) No. 327/2011. Compliance with these efficiency requirements is a prerequisite for these products to acquire the CE-certification. External rotor motors are not affected by the motor regulation.
Most ZIEHL-ABEGG fans exceed the ErP requirements both in AC as well as in EC technology and are well equipped for future requirements.
-
Information-ErP-Directive-2013.pdf (1 MB)
-
ErP-Data-for-Centrifugal-fans-for-air-handling-units-2011.pdf (752 KB)
Measurement category | Axial fan | Centrifugal forward curved fan | Centrifugal backward curved fan without housing | Centrifugal backward curved fan with housing | Mixed flow fan | Cross flow fan | |
---|---|---|---|---|---|---|---|
Tier 1 01.01.2013 |
A, C | 36 | 37 | 58 | 58 | 47 | |
B, D | 50 | 42 | 61 | 58 | 13 | ||
Tier 2 01.01.2015 |
A, C | 40 | 44 | 62 | 61 | 50 | |
B, D | 58 | 49 | 64 | 62 | 21 |
For motors there is only product information for internal rotor motors made by ZIEHL-ABEGG, for other brands please ask the manufacturer
Note!
Product is not ErP-relevant or does not exist