Electrical data
3~400V D/Y 50Hz P1 940/680W
2.8/1.45A ΔI=0% 950/820/min COSY 0,48 70°C
Pstat = 0 Pa: 970/ 910 min 0,62/0,48 (W) kW 3,90/3,70 m3/s
3~400V D/Y 60Hz P1 1,40/0,78kW
3.1/1.65A ΔI=0% 1090/780/min COSY 0,65 70°C
Pstat = 0 Pa: 1140/ 940 min 0,90/0,64 (W) kW 4,60/3,80 m3/s
460V D/Y 60Hz P1 1,50/0,96kW
3,10/ 1,80A ΔI=0% 1120/880/minCOSY 0,59 70°C
Pstat = 0 Pa: 1160/1020 min 0,96/0,74 (W) kW 4,70/4,10 m3/s
Technical data
Electrical connection: Terminal box
Number of blades: 5
Thermal class: THCL155
Degree of protection: IP54
Motor protection: thermal contact
blades made of High Performance Composite Material, Blades 2 coat paint, RAL 9006 (white aluminium)
Rotor: Aluminium, Rotor 2 coat paint, RAL 9006 (white aluminium)
Conformity: ErP 2015, ErP NEIN
ErP-data
Efficiency ΗstatA: 39.2 %
Efficiency grade: Nactual = 45.9 / Ntarget = 40*
*ErP 2015
Additional DoE and CT20 relevant product information:Selected product is eligible for use in the U.S. under exception stated in 10 CFR Part 431.174 paragraph A(3), as our Customer we recommend you verify local compliance prior to use.