Electrical data
3~400V D/Y 50Hz P1 880/620W
2.3/1.25A ΔI=0% 550/450/min COSY 0,57 70°C
Pstat = 0 Pa: 570/ 500 min 0,64/0,46 (W) kW 6,60/5,90 m3/s
3~400V D/Y 60Hz P1 1,30/0,70kW
2.6/1.5A ΔI=5% 610/400/min COSY 0,71 70°C
Pstat = 0 Pa: 650/ 500 min 0,90/0,62 (W) kW 7,70/5,90 m3/s
460V D/Y 60Hz P1 1,40/0,88kW
2,60/ 1,55A ΔI=5% 640/470/minCOSY 0,67 70°C
Pstat = 0 Pa: 670/ 560 min 0,98/0,70 (W) kW 7,80/6,60 m3/s
Technical data
Electrical connection: Terminal box
Number of blades: 5
Thermal class: THCL155
Degree of protection: IP54
Motor protection: thermal contact
impeller made of aluminium, Blades 2 coat paint, RAL 9005 (jet black)
Rotor: Aluminium, Rotor 2 coat paint, RAL 9005 (jet black)
Conformity: ErP 2026, ErP 2026
ErP-data
Efficiency ΗstatA: 42.1 %
Efficiency grade: Nactual = 53.5 / Ntarget = 50*
*ErP 2026
Additional DoE and CT20 relevant product information:Selected product is eligible for use in the U.S. under exception stated in 10 CFR Part 431.174 paragraph A(3), as our Customer we recommend you verify local compliance prior to use.